Protocol 112 of 81Layer 7FrameAssembly v3.3.0
Raw .mdllms-full.txt
iec104IEC 60870-5-104 Substation Telecontrol Over TCP/IP

iec104 — Port 2404 IEC 60870-5-104 Substation I/S/U APDUs

Default Port / Protocol
TCP 2404
Host Endpoint Rule
Dual-Stack IPv4/IPv6
Wireshark Display Filter
iec60870_104
Standards & Specs
IEC 60870-5-104, IEC 60870-5-101
Wire Stack:Ethernet II[802.1Q / QinQ / MPLS]IPv4 / IPv6TCP 2404IEC 60870-5-104
L2 Tagging: vlan · qinq · repeatable mpls · fcsHost Family: Dual-Stack IPv4/IPv6L3 QoS & TTL: ttl · dscp · ecnL4 State: Auto 4-tuple seq / acknum

What It Does on the Wire

European and Asian transmission grids run on TCP 2404 (0x68 APCI start byte): iec104 encodes startdt/testfr U-frames, sframe acknowledgments, and IEEE-754 real or integer ASDUs (typeid, cot, ca, ioa).

IEC 60870-5-104 (iec104) is the dominant transmission and distribution power-grid SCADA telecontrol protocol across Europe, Asia, and Latin America (and notorious from the 2016 Industroyer / CrashOverride Ukraine substation incident) on TCP port 2404. Every APDU starts with 0x68, an 8-bit APDU Length, and 4 Application Protocol Control Information (APCI) control octets encoding U-Frames (STARTDT act/con, STOPDT, TESTFR), S-Frames (Supervisory N(R) acknowledgments), or I-Frames (N(S)/N(R) sequence numbers + an IEC 60870-5-101 ASDU: TypeID, VSQ, Cause of Transmission cot, 16-bit Common Address ca, 24-bit Information Object Address ioa, and integer or IEEE 754 real telemetry/command values).

FrameAssembly encodes shifted little-endian (seq << 1) I/S-frame control fields, 16-bit ca, 24-bit ioa, and IEEE 754 single-precision floats (real 49.98 -> TypeID 13 M_ME_NC_1 Short Floating Point).

01. Application

Industroyer / Substation Breaker Command (TypeID 45/46) IDS Detection

Test Suricata, Zeek, Claroty, and Dragos rules against unauthorized Single Command (typeid 45 C_SC_NA_1) and Double Command (typeid 46 C_DC_NA_1, cot 6 Activation) frames targeting substation RTU ioa addresses.

02. Application

Control-Center <-> RTU STARTDT Handshake & Periodic Grid Telemetry

Script startdt -> startdt confirm -> M_ME_NC_1 (typeid 13, real 50.01 Hz / 230.4 kV) -> sframe supervisory ACK -> testfr keepalives.

03. Application

Substation DMZ Firewall Deep Inspection (ca & typeid Whitelisting)

Verify OT firewalls allow read/spontaneous telemetry (typeid 1..36, cot 3 Spontaneous / cot 20 Interrogation) while blocking write/control typeid 45..64 from historian subnets.

Fig. 1 · RFC Octet & Bit Schematic

RFC Wire Header Layout (iec104)

Select any 32-bit wire word or field slice below to inspect which .frasm modifiers control those octets and what defaults the compiler writes.

0 ··············· 15 · 16 ··············· 31 bit
Selected Wire Segment
IEC 60870-5-104 Wire PDU & Payload (Variable)
Controlling .frasm Modifiers
iec104 startdt · txseq · typeid · cot · ca · payload · hexpayload
Compiler Default Behavior
RFC-compliant IEC 60870-5-104 defaults (IEC 60870-5-104)
Wireshark Dissection Note · Inspecting IEC 60870-5-104 APCI & ASDU Objects on TCP 2404

Filter with iec60870_104 (or 104apci / 104asdu) on TCP 2404 to verify 0x68 APCI U/S/I frames, Send/Receive sequence numbers, TypeID, Cause of Transmission (COT), Common Address, and IOA values.

Minimal Quickstart (iec104_quickstart.frasm)

Select Preview Packets to compile in-browser and inspect timestamps + wire byte lengths, or open directly in the Playground.

iec104_quickstart.frasm11 lines
Open in Playground
host scada_cc { ip 10.104.1.10 }
host sub_rtu { ip 10.104.2.50 }
compile {
scada_cc -> sub_rtu tcp syn srcport 52404 dstport 2404 wait 1ms
scada_cc <- sub_rtu tcp syn ack wait 1ms
scada_cc -> sub_rtu tcp ack wait 1ms
scada_cc -> sub_rtu iec104 startdt wait 2ms
scada_cc <- sub_rtu iec104 startdt confirm wait 5ms
scada_cc <- sub_rtu iec104 txseq 0 rxseq 0 typeid 13 cot 3 ca 1 ioa 1001 real 49.98
}

Handled Automatically on the Wire

  • Defaults to stateful TCP port 2404 and formats the 0x68 Start Byte + exact APDU Length (4 for U/S-frames, 4 + ASDU_len for I-frames).
  • Encodes 15-bit txseq and rxseq shifted left by 1 bit (seq << 1) in little-endian APCI octets per IEC 60870-5-104 Section 5.1.
  • Packs 16-bit little-endian Common Address (ca), 24-bit little-endian Information Object Address (ioa), Quality Descriptor (QDS = 0x00 Good), and 32-bit IEEE 754 little-endian floats when real is provided.
Multi-Frame Example

Substation Telecontrol Session: U-Frame STARTDT, Spontaneous 50Hz Float Telemetry, S-Frame & Single Command

Activates data transfer (STARTDT act/con), streams spontaneous grid frequency telemetry (TypeID 13, 49.98 Hz), acknowledges via S-Frame, executes a Single Command (TypeID 45, cot 6 -> cot 7), and exchanges TESTFR keepalives.

iec104_substation_telecontrol.frasm21 lines
Open in Playground
host dispatch_cc { ip 172.26.1.10 }
host bay_rtu_04 { ip 172.26.4.40 }
compile {
dispatch_cc -> bay_rtu_04 tcp syn srcport 54404 dstport 2404 wait 1ms
dispatch_cc <- bay_rtu_04 tcp syn ack wait 1ms
dispatch_cc -> bay_rtu_04 tcp ack wait 1ms
// 1. U-Frame STARTDT act (0x07) & STARTDT con (0x0b)
dispatch_cc -> bay_rtu_04 iec104 startdt wait 2ms
dispatch_cc <- bay_rtu_04 iec104 startdt confirm wait 5ms
// 2. I-Frame Spontaneous Measured Float (TypeID 13 M_ME_NC_1, COT 3 Spontaneous, IOA 4001 = 49.98 Hz)
dispatch_cc <- bay_rtu_04 iec104 txseq 0 rxseq 0 typeid 13 cot 3 ca 4 ioa 4001 real 49.98 wait 2ms
// 3. Supervisory S-Frame acknowledging RTU txseq 0 (rxseq = 1)
dispatch_cc -> bay_rtu_04 iec104 sframe rxseq 1 wait 10ms
// 4. Breaker Single Command (TypeID 45 C_SC_NA_1, COT 6 Activation -> COT 7 ActivationCon)
dispatch_cc -> bay_rtu_04 iec104 txseq 0 rxseq 1 typeid 45 cot 6 ca 4 ioa 6001 value 1 wait 3ms
dispatch_cc <- bay_rtu_04 iec104 txseq 1 rxseq 1 typeid 45 cot 7 ca 4 ioa 6001 value 1 wait 15ms
// 5. U-Frame TESTFR act & con keepalive
dispatch_cc -> bay_rtu_04 iec104 testfr wait 2ms
dispatch_cc <- bay_rtu_04 iec104 testfr confirm
}
Terminal Commands (FrameAssembly CLI v3.3.0)
# 1. Eyeball relative timestamps, ports & wire lengths in your terminal
frameassembly show iec104_substation_telecontrol.frasm

# 2. Compile .frasm -> classic .pcap, nanosecond .pcapng, or pipe via '-'
frameassembly iec104_substation_telecontrol.frasm iec104_substation_telecontrol.pcap
frameassembly iec104_substation_telecontrol.frasm iec104_substation_telecontrol.pcapng

# 3. Round-trip .pcap <-> .frasm whenever you want to scrub or tweak an existing capture
frameassembly reverse iec104_substation_telecontrol.pcap iec104_substation_telecontrol_edited.frasm

# 4. Verify dissected protocol fields in tshark
tshark -r iec104_substation_telecontrol.pcap -Y "iec60870_104"

All iec104 Keywords & Header Options

Every sub-keyword and header option is lowercase [a-z0-9]+ with zero underscores — mix and match them in any order after iec104:

src_host -> dst_host iec104 [startdt | stopdt | testfr | sframe | msgtype "<text>"] [confirm] [txseq <0..32767>] [rxseq <0..32767>] [typeid <0..255>] [cot "<text_or_num>"] [ca <0..65535>] [ioa <0..16777215>] [value <number>] [real <decimal>]
Keyword / OptionAccepted ValueDefaultEffect on Packet
startdt | stopdt | testfr | sframe | msgtype "<text>" | [confirm]APCI frame format (U-Frame STARTDT/STOPDT/TESTFR, S-Frame, or default I-Frame when ASDU fields are present)I-Frame (or U-Frame when startdt/stopdt/testfr is set)Selects U-Frame (0x07/0x0b STARTDT, 0x13/0x23 STOPDT, 0x43/0x83 TESTFR with confirm), S-Frame (0x01), or I-Frame (N(S)/N(R) + ASDU).
txseq <0..32767> | rxseq <0..32767>15-bit Send N(S) & Receive N(R) sequence numberstxseq 0, rxseq 0Encodes (txseq << 1) and (rxseq << 1) in APCI control octets 1..4.
typeid <0..255>8-bit IEC 60870-5-101/104 Type Identification13 (M_ME_NC_1 when real is set) or 1 (M_SP_NA_1)Sets ASDU byte 0 (1 Single-Point, 9 Normalized Meas, 13 Short Float, 36 Float w/ CP56Time2a, 45 Single Cmd, 46 Double Cmd, 100 Interrogation).
cot "<text_or_num>"Cause of Transmission (3 Spont, 6 Act, 7 ActCon, 10 ActTerm, 20 Interrogated)3 (Spontaneous)Writes the 16-bit Cause of Transmission field in the ASDU header.
ca <0..65535> | ioa <0..16777215>16-bit Common Address of ASDU & 24-bit Information Object Addressca 1, ioa 1Writes the 2-byte little-endian station CA and 3-byte little-endian data-point IOA.
value <number> | real <decimal>Integer state/command byte or IEEE 754 floating-point number (e.g. 49.98, -12.5)value 1Encodes Single/Double/Measured integer values (value) or 4-byte IEEE 754 float + QDS (real).

Cross-Layer Wrappers Valid with iec104

802.1Q VLAN / QinQ / MPLS tags, IPv4/IPv6 QoS & TTL fields, wait gaps, and transport overrides allowed on this protocol

15 options
OptionRange / FormatDefaultEffect on Packet
wait <number><ns|us|ms|s|m>Time gap (ns, us, ms, s, m)10msAdvances the packet timestamp clock after sending this packet and before the next packet (wait 0ns sends back-to-back).
comment "<text>"Quoted UTF-8 annotationOmittedAttaches an Enhanced Packet Block opt_comment annotation when compiling to .pcapng (Wireshark pkt_comment filter).
payload "<text>" | hexpayload "<hex>"Quoted text or hex bytes (choose one)OmittedAppends or overrides raw payload bytes ("deadbeef", "de:ad:be:ef", or "\x01\x02") and updates packet lengths and checksums.
srcmac <mac> | dstmac <mac> | ethertype <0..65535>Colon/hyphen/Cisco MAC · EtherType 0..65535 (e.g. 0x0800)Host MAC / RFC multicast MAC / auto EtherTypeOverrides the 14-byte Ethernet II source MAC, destination MAC, or standalone Layer 2 16-bit EtherType.
fcs | badfcsEthernet CRC-32 trailer flags (choose one)Omittedfcs appends a valid IEEE 802.3 4-byte CRC-32 Frame Check Sequence trailer; badfcs XOR-corrupts the CRC-32 for NIC/tap negative tests.
vlan <0..4095> [pcp <0..7>] [dei <0|1>]VLAN ID 0..4095, PCP 0..7, DEI 0..1UntaggedWraps the packet in an IEEE 802.1Q VLAN tag (0x8100) with optional 802.1p QoS priority.
qinq <0..4095> [innervlan <0..4095>]Outer S-VLAN 0..4095, Inner C-VLAN 0..4095Untagged (innervlan 1 when qinq is set)Double-tags the packet with outer IEEE 802.1ad S-Tag (0x88a8) plus inner IEEE 802.1Q C-Tag (0x8100).
mpls <0..1048575> [label <0..1048575>] [exp|tc <0..7>] [bos <0|1>] [mplsttl <0..255>]Repeatable label stack (0..1048575, exp/tc 0..7, bos 0..1, ttl 0..255)Unlabeled (auto bos=0 on outer labels, bos=1 on bottom)Prepends one or more 32-bit MPLS label shims (0x8847, e.g. mpls 16000 mpls 24010) ahead of Layer 2 EoMPLS or Layer 3 payloads.
ttl <0..255> [dscp <0..63>] [ecn <0..3>]TTL/Hop Limit 0..255, DSCP 0..63, ECN 0..3ttl 64, dscp 0, ecn 0Sets IPv4 TTL or IPv6 Hop Limit plus DiffServ (DSCP) and ECN QoS markings.
ipid <0..65535> [df] [mf] [fragoffset <0..8191>] [routeralert] [badipchecksum]IPv4 ID, DF/MF flags, offset 0..8191, Router Alert & checksum faultipid 1, flags 0, fragoffset 0, valid RFC 1071 checksumSets IPv4 Identification/fragmentation, injects RFC 2113 Router Alert (20 04 00 00), or corrupts the 16-bit IPv4 header checksum (badipchecksum).
flowlabel <0..1048575>20-bit IPv6 Flow Label (0..1048575)0Sets the 20-bit IPv6 Flow Label for ECMP routing tests (valid on IPv6 endpoint pairs only).
srcport <0..65535> | dstport <0..65535>Port number 0..65535srcport 49152 (remembered), TCP 2404Overrides source or destination port and remembers the port pair automatically on <- replies.
transport sctpOptional SCTP association transport (IP Proto 132)TCP (TCP 2404)Carries this Layer 7 PDU inside a stateful RFC 9260 SCTP DATA chunk with automatic Verification Tag, TSN tracking, and CRC-32c.
badchecksumL4/ICMP/SCTP checksum fault injection flagValid RFC checksum / CRC-32cDeliberately corrupts the TCP, SCTP CRC-32c, ICMP, or ICMPv6 checksum for negative IDS/firewall testing.
seq <number> | acknum <number> | win|window <0..65535> | urgent <0..65535> | syn | ack | psh | fin | rst | urg | ece | cwrTCP sequence/ack numbers, window, flags, SACK, TCP-MD5 & TFO optionspsh ack, win 65535, automatic TCP seq/acknumOverrides automatic TCP sequence tracking, flags, or RFC 7323/2018/2385/7413 options (mss, wscale, sackperm, sackblock, tsval, tsecr, tcpmd5, tfo).

Gotchas & Quick Fixes

Combine startdt/testfr with confirm (Not response) for U-Frame Confirmations

Rejected
cc <- rtu iec104 startdt response
Valid v3.3.0 Syntax
cc <- rtu iec104 startdt confirm

IEC 60870-5-104 U-Frames pair Activation (act) with Confirmation (con, enabled via the confirm flag keyword).

Do Not Include typeid/ioa on Pure U-Frames If You Want a 6-Byte APCI Packet

Rejected
cc -> rtu iec104 startdt ca 1 ioa 1001 real 49.98
Valid v3.3.0 Syntax
cc -> rtu iec104 startdt cc <- rtu iec104 typeid 13 cot 3 ca 1 ioa 1001 real 49.98

Real substations exchange 6-byte U-Frame STARTDT act / STARTDT con packets first before transmitting ASDU I-Frames (ca, ioa, real).

Field Guide 03
Poke Stateful Firewalls, Suricata, Zeek & OT Conduits