s7comm — Port 102 TPKT/COTP Siemens S7 Reads, Writes & Stop
- Default Port / Protocol
- TCP 102 (ISO-on-TCP)
- Host Endpoint Rule
- Dual-Stack IPv4/IPv6
- Wireshark Display Filter
- s7comm
- Standards & Specs
- RFC 1006 (TPKT), ISO 8073 (COTP), Siemens S7comm
What It Does on the Wire
Wrapped inside RFC 1006 TPKT + ISO 8073 COTP on TCP 102, s7comm builds Siemens 0x32 readvar, writevar, and high-severity plcstop frames so you can verify OT IDS signatures safely.
Siemens S7 Communication (s7comm) connects TIA Portal / STEP 7 engineering stations and WinCC HMIs to SIMATIC S7-300, S7-400, S7-1200, and S7-1500 PLCs over ISO-on-TCP port 102. Every S7comm packet wraps the 0x32 S7 PDU inside a 4-byte RFC 1006 TPKT header (0x03 0x00 + 16-bit total length) and a 3-byte ISO 8073 COTP Data header (0x02 0xf0 0x80).
FrameAssembly builds the complete TPKT + COTP + S7comm stack for connection negotiation (setupcomm), Data Block variable reads (readvar), variable writes (writevar), and high-impact plccontrol CPU Run/Stop commands—ideal for testing IEC 62443 OT firewalls and ICS threat detections safely offline.
Test OT IDS Alarms for PLCControl Stop & Unauthorized WriteVar
Generate s7comm rosctr "job" plccontrol (0x28) and writevar area 0x84 dbnum 1 packets to verify Claroty, Dragos, Nozomi, Zeek, and Suricata Siemens S7 alerts without touching a running PLC.
Purdue Level 1/2 Industrial Firewall Conduit Verification (TCP 102)
Confirm cell/area firewalls permit readvar from approved WinCC HMI IPs while blocking engineering writevar / plccontrol from unauthorized subnets.
Validate S7 Data Block (DB) Historian Polling Parsers
Pair rosctr "job" readvar requests with rosctr "ackdata" PLC replies carrying matched pduref IDs.
RFC Wire Header Layout (s7comm)
Select any 32-bit wire word or field slice below to inspect which .frasm modifiers control those octets and what defaults the compiler writes.
Wireshark dissects RFC 1006 TPKT (4 B) -> ISO 8073 COTP -> Siemens S7comm (0x32 magic) in order; filter with s7comm to jump straight to Job / Ack_Data parameters.
Minimal Quickstart (s7comm_quickstart.frasm)
Select Preview Packets to compile in-browser and inspect timestamps + wire byte lengths, or open directly in the Playground.
host wincc_hmi { ip 192.168.10.20 }
host s7_plc { ip 192.168.10.100 }
compile {
wincc_hmi -> s7_plc tcp syn srcport 50102 dstport 102 wait 1ms
wincc_hmi <- s7_plc tcp syn ack wait 1ms
wincc_hmi -> s7_plc tcp ack wait 1ms
wincc_hmi -> s7_plc s7comm rosctr "job" setupcomm pduref 1 wait 2ms
wincc_hmi <- s7_plc s7comm rosctr "ackdata" setupcomm pduref 1 wait 2ms
wincc_hmi -> s7_plc s7comm rosctr "job" readvar pduref 2 area 0x84 dbnum 1 offset 0 count 4
}Handled Automatically on the Wire
- Defaults to TCP destination port
102(psh ack) and computes the outer 4-byte TPKT (0x03 0x00 <len>) + 3-byte COTP DT (0x02 0xf0 0x80) framing automatically. - Writes the
0x32S7 Protocol ID, ROSCTR (0x01Job,0x02Ack,0x03Ack_Data,0x07Userdata), 2-byte error class/code onackdata, and exact Parameter/Data lengths. - Encodes 12-byte S7Any (
0x12 0x0a 0x10) variable item addressing (area,dbnum, bit-shiftedoffset * 8, andcount) automatically onreadvar/writevarJobs.
S7 Communication Setup, DB1 Read Poll, DB1 Write & PLC CPU Control Alert
Negotiates S7 PDU parameters (setupcomm), polls 4 bytes from DB1.DBB0 (area 0x84 dbnum 1), writes to DB1, and emits a plccontrol Job to test critical OT security alerts.
host tia_ws { ip 10.110.1.15 }
host plc_315 { ip 10.110.2.102 }
compile {
tia_ws -> plc_315 tcp syn srcport 51102 dstport 102 win 65535 mss 1460 wait 1ms
tia_ws <- plc_315 tcp syn ack win 65535 mss 1460 wait 1ms
tia_ws -> plc_315 tcp ack wait 1ms
// 1. S7 Setup Communication (Func 0xf0)
tia_ws -> plc_315 s7comm rosctr "job" setupcomm pduref 100 wait 2ms
tia_ws <- plc_315 s7comm rosctr "ackdata" setupcomm pduref 100 wait 2ms
// 2. Read 4 bytes from Data Block 1 (area 0x84 = DB, dbnum 1, offset 0)
tia_ws -> plc_315 s7comm rosctr "job" readvar pduref 101 area 0x84 dbnum 1 offset 0 count 4 wait 2ms
tia_ws <- plc_315 s7comm rosctr "ackdata" readvar pduref 101 count 4 wait 5ms
// 3. WriteVar (0x05) + PLCControl (0x28) -> critical OT IDS signatures
tia_ws -> plc_315 s7comm rosctr "job" writevar pduref 102 area 0x84 dbnum 1 offset 0 count 2 wait 3ms
tia_ws <- plc_315 s7comm rosctr "ackdata" writevar pduref 102 wait 3ms
tia_ws -> plc_315 s7comm rosctr "job" plccontrol pduref 103
}# 1. Eyeball relative timestamps, ports & wire lengths in your terminal
frameassembly show s7comm_plc_security_lab.frasm
# 2. Compile .frasm -> classic .pcap (tcpdump/tcpreplay/Suricata) or nanosecond .pcapng
frameassembly s7comm_plc_security_lab.frasm s7comm_plc_security_lab.pcap
frameassembly s7comm_plc_security_lab.frasm s7comm_plc_security_lab.pcapng
# 3. Round-trip .pcap <-> .frasm whenever you want to scrub or tweak an existing capture
frameassembly reverse s7comm_plc_security_lab.pcap s7comm_plc_security_lab_edited.frasm
# 4. Verify dissected protocol fields in tshark
tshark -r s7comm_plc_security_lab.pcap -Y "s7comm"All s7comm Keywords & Header Options
Every sub-keyword and header option is lowercase [a-z0-9]+ with zero underscores — mix and match them in any order after s7comm:
src_host -> dst_host s7comm [setupcomm | readvar | writevar | plccontrol | func "<text>"] [rosctr "<job|ack|ackdata|userdata>"] [pduref <0..65535>] [area <hex_or_str>] [dbnum <0..65535>] [offset <number>] [count <0..65535>]| Keyword / Option | Accepted Value | Default | Effect on Packet |
|---|---|---|---|
| setupcomm | readvar | writevar | plccontrol | func "<text>" | S7 Parameter Function (0xf0 Setup, 0x04 ReadVar, 0x05 WriteVar, 0x28 PLCControl) | setupcomm (0xf0) | Selects the S7comm Parameter Function code. |
| rosctr "<job|ack|ackdata|userdata>" | Remote Operating Service Control type | "job" (0x01) | Sets 0x01 Job (HMI/engineering request), 0x02 Ack, 0x03 Ack_Data (PLC reply with 2-byte error status), or 0x07 Userdata. |
| pduref <0..65535> | 16-bit PDU Reference ID | 1 | Correlates each PLC ackdata response with its initiating job. |
| area <hex_or_str> | dbnum <0..65535> | 0x84 Data Blocks (DB), 0x81 Inputs (I), 0x82 Outputs (Q), 0x83 Merkers (M) + DB number | area 0x84 (DB), dbnum 1 | Sets the memory area and Data Block number in S7Any item addressing. |
| offset <number> | count <0..65535> | Byte offset + item byte count | offset 0, count 1 | Encodes the 24-bit bit-addressed start offset and 16-bit read/write length. |
Cross-Layer Wrappers Valid with s7comm
802.1Q VLAN / QinQ / MPLS tags, IPv4/IPv6 QoS & TTL fields, wait gaps, and transport overrides allowed on this protocol
11 options
Cross-Layer Wrappers Valid with s7comm
802.1Q VLAN / QinQ / MPLS tags, IPv4/IPv6 QoS & TTL fields, wait gaps, and transport overrides allowed on this protocol
| Option | Range / Format | Default | Effect on Packet |
|---|---|---|---|
| wait <number><ns|us|ms|s|m> | Time gap (ns, us, ms, s, m) | 10ms | Advances the packet timestamp clock after sending this packet and before the next packet (wait 0ns sends back-to-back). |
| payload "<text>" | hexpayload "<hex>" | Quoted text or hex bytes (choose one) | Omitted | Appends or overrides raw payload bytes ("deadbeef" or "de:ad:be:ef") and updates packet lengths and checksums. |
| srcmac <mac> | dstmac <mac> | ethertype <0..65535> | Colon/hyphen/Cisco MAC · EtherType u16 (e.g. 0x0800) | Host MAC / RFC multicast MAC / auto EtherType | Overrides the 14-byte Ethernet II source MAC, destination MAC, or 16-bit EtherType for this single packet. |
| vlan <0..4095> [pcp <0..7>] [dei <0|1>] | VLAN ID 0..4095, PCP 0..7, DEI 0..1 | Untagged | Wraps the packet in an IEEE 802.1Q VLAN tag (0x8100) with optional 802.1p QoS priority. |
| qinq <0..4095> [innervlan <0..4095>] | Outer S-VLAN 0..4095, Inner C-VLAN 0..4095 | Untagged (innervlan 1 when qinq is set) | Double-tags the packet with outer IEEE 802.1ad S-Tag (0x88a8) plus inner IEEE 802.1Q C-Tag (0x8100). |
| mpls <0..1048575> [label <0..1048575>] [exp|tc <0..7>] [bos <0|1>] [mplsttl <0..255>] | Label 0..1048575, exp/tc 0..7, bos 0..1, ttl 0..255 | Unlabeled (at most 1 mpls tag per packet) | Inserts a 32-bit MPLS label header (0x8847) ahead of the Layer 3 header. |
| ttl <0..255> [dscp <0..63>] [ecn <0..3>] | TTL/Hop Limit 0..255, DSCP 0..63, ECN 0..3 | ttl 64, dscp 0, ecn 0 | Sets IPv4 TTL or IPv6 Hop Limit plus DiffServ (DSCP) and ECN QoS markings. |
| ipid <0..65535> [df] [mf] [fragoffset <0..8191>] | IPv4 ID, DF/MF flags, fragment offset 0..8191 | ipid 1, flags 0, fragoffset 0 | Sets IPv4 Identification, Do-Not-Fragment (df), More-Fragments (mf), and fragment offset (ignored over IPv6). |
| flowlabel <0..1048575> | 20-bit IPv6 Flow Label (0..1048575) | 0 | Sets the 20-bit IPv6 Flow Label for ECMP routing tests (ignored when running over IPv4 hosts). |
| srcport <0..65535> | dstport <0..65535> | Port number 0..65535 | srcport 49152 (remembered), TCP 102 (ISO-on-TCP) | Overrides source or destination port and remembers the port pair automatically on <- replies. |
| seq <number> | acknum <number> | win|window <0..65535> | urgent <0..65535> | syn | ack | psh | fin | rst | urg | ece | cwr | TCP sequence/ack numbers, window size, flags & RFC 7323 options | psh ack, win 65535, automatic TCP seq/acknum | Overrides automatic TCP sequence tracking, flags, or RFC 7323 options (mss, wscale, sackperm, tsval, tsecr). |
Gotchas & Quick Fixes
Set rosctr "ackdata" on <- PLC Replies
wincc_hmi <- s7_plc s7comm readvar pduref 2 count 4wincc_hmi <- s7_plc s7comm rosctr "ackdata" readvar pduref 2 count 4rosctr defaults to "job" (a request from HMI to PLC). On <- replies from the PLC, specify rosctr "ackdata" so the 12-byte S7 Ack_Data header (with Error Class/Code 0x0000) is written.