bsap — Port 1234 Bristol Babcock BSAP Water & Pipeline Telemetry
- Default Port / Protocol
- UDP 1234 (or TCP 1234 via transport tcp)
- Host Endpoint Rule
- Dual-Stack IPv4/IPv6
- Wireshark Display Filter
- udp.port == 1234 || tcp.port == 1234
- Standards & Specs
- Emerson OpenBSI / Bristol Babcock ControlWave BSAP IP Specification
What It Does on the Wire
Municipal water distribution and gas SCADA RTUs using ControlWave / Bristol Babcock controllers run BSAP on port 1234 — bsap constructs IP RBE headers plus Remote Database poll, read, and write frames.
Bristol Synchronous Asynchronous Protocol over IP (bsap) connects Emerson ControlWave, Bristol Babcock Network 3000 / DPC 3330 RTUs, and OpenBSI SCADA masters across municipal water/wastewater distribution and natural-gas SCADA networks on UDP or TCP port 1234. BSAP/IP encapsulates Remote Database Access (RDB / NDB) and poll messages with 16-bit Destination Address (dst), 16-bit Source Address (src), 8-bit Sequence Number (seqnum), Application Function Code (poll, read RDB Read, write RDB Write), starting signal/list addr, count, and 32-bit value payloads.
FrameAssembly encodes BSAP/IP headers and RDB payloads cleanly over default UDP 1234 or stateful TCP 1234 (transport tcp).
Municipal Water & Gas Distribution SCADA Firewall Rules (Port 1234)
Verify SCADA DMZ firewalls restrict UDP/TCP 1234 strictly to authorized OpenBSI / TopServer masters and ControlWave RTU IPs, blocking stray internet/IT scanning on port 1234.
OT IDS Detection of Unauthorized ControlWave RDB Writes (bsap write)
Generate bsap poll and bsap read baseline traffic followed by an unauthorized bsap write to pump/valve signal addresses to validate Dragos, Claroty, and Nozomi alerts.
Radio / Cellular BSAP/UDP vs Leased-Line BSAP/TCP (transport tcp)
Test SCADA front-end processors across both connectionless UDP 1234 telemetry and TCP 1234 (transport tcp) sessions.
RFC Wire Header Layout (bsap)
Select any 32-bit wire word or field slice below to inspect which .frasm modifiers control those octets and what defaults the compiler writes.
Minimal Quickstart (bsap_quickstart.frasm)
Select Preview Packets to compile in-browser and inspect timestamps + wire byte lengths, or open directly in the Playground.
host openbsi_srv { ip 10.123.1.10 }
host cw_rtu_10 { ip 10.123.4.10 }
compile {
openbsi_srv -> cw_rtu_10 bsap read dst 10 src 1 seqnum 1 addr 100 count 2 wait 5ms
openbsi_srv <- cw_rtu_10 bsap read isresponse dst 1 src 10 seqnum 1 addr 100 value 420
}Handled Automatically on the Wire
- Defaults to UDP destination port
1234(transport tcpswitches to stateful TCP1234) and calculates the BSAP/IP message length header automatically. - Encodes 16-bit BSAP node addresses (
dst,src), 8-bitseqnum, and RDB function codes (poll,read,write, plus response flag bit whenisresponseis set). - Packs 16-bit signal
addr, itemcount, and 32-bit datavaluefields for RDB Read responses and RDB Write commands.
Water Booster Station ControlWave RTU Cycle: BSAP Poll, Tank Level Read & Pump Setpoint Write
Polls ControlWave RTU 10 over UDP 1234, reads reservoir level RDB addr 200, and issues an RDB write (addr 205, value 65) with RTU acknowledgment.
host water_scada { ip 172.24.12.5 }
host booster_rtu { ip 172.24.12.50 }
compile {
// 1. BSAP Node Status Poll (seqnum 1) -> RTU Response
water_scada -> booster_rtu bsap poll dst 50 src 1 seqnum 1 wait 4ms
water_scada <- booster_rtu bsap poll isresponse dst 1 src 50 seqnum 1 wait 10ms
// 2. Remote Database (RDB) Read of Reservoir Tank Level (addr 200, count 2)
water_scada -> booster_rtu bsap read dst 50 src 1 seqnum 2 addr 200 count 2 wait 5ms
water_scada <- booster_rtu bsap read isresponse dst 1 src 50 seqnum 2 addr 200 value 1840 wait 15ms
// 3. RDB Write of Booster Pump VFD Speed Setpoint (addr 205 = 65%)
water_scada -> booster_rtu bsap write dst 50 src 1 seqnum 3 addr 205 count 1 value 65 wait 5ms
water_scada <- booster_rtu bsap write isresponse dst 1 src 50 seqnum 3 addr 205 value 65
}# 1. Eyeball relative timestamps, ports & wire lengths in your terminal
frameassembly show bsap_controlwave_scada.frasm
# 2. Compile .frasm -> classic .pcap, nanosecond .pcapng, or pipe via '-'
frameassembly bsap_controlwave_scada.frasm bsap_controlwave_scada.pcap
frameassembly bsap_controlwave_scada.frasm bsap_controlwave_scada.pcapng
# 3. Round-trip .pcap <-> .frasm whenever you want to scrub or tweak an existing capture
frameassembly reverse bsap_controlwave_scada.pcap bsap_controlwave_scada_edited.frasm
# 4. Verify dissected protocol fields in tshark
tshark -r bsap_controlwave_scada.pcap -Y "udp.port == 1234 || tcp.port == 1234"All bsap Keywords & Header Options
Every sub-keyword and header option is lowercase [a-z0-9]+ with zero underscores — mix and match them in any order after bsap:
src_host -> dst_host bsap [read | write | poll | func "<text_or_num>"] [dst <0..65535>] [src <0..65535>] [seqnum <0..255>] [addr <0..65535>] [count <0..65535>] [value <number>] [isresponse] [transport <udp|tcp>]| Keyword / Option | Accepted Value | Default | Effect on Packet |
|---|---|---|---|
| read | write | poll | func "<text_or_num>" | [isresponse] | BSAP Application Function selector + Response flag | poll, request | Selects Poll, RDB Read, RDB Write, or numeric BSAP function byte and toggles response direction. |
| dst <0..65535> | src <0..65535> | 16-bit BSAP Destination & Source RTU/Master Node Addresses | dst 1, src 0 | Writes the 2-byte Destination and Source BSAP node addresses in the BSAP/IP header. |
| seqnum <0..255> | 8-bit BSAP Message Sequence Number (0..255) | 1 | Writes the 1-byte transaction Sequence Number echoed by the RTU. |
| addr <0..65535> | count <0..65535> | value <number> | 16-bit RDB Signal Index/Address, Point Count, and 32-bit Signal Value | addr 1, count 1, value 0 | Populates RDB Read/Write request lists and data values. |
| transport <udp|tcp> | udp or tcp | udp | Switches Layer 4 between BSAP/UDP (1234) and BSAP/TCP (1234). |
Cross-Layer Wrappers Valid with bsap
802.1Q VLAN / QinQ / MPLS tags, IPv4/IPv6 QoS & TTL fields, wait gaps, and transport overrides allowed on this protocol
15 options
Cross-Layer Wrappers Valid with bsap
802.1Q VLAN / QinQ / MPLS tags, IPv4/IPv6 QoS & TTL fields, wait gaps, and transport overrides allowed on this protocol
| Option | Range / Format | Default | Effect on Packet |
|---|---|---|---|
| wait <number><ns|us|ms|s|m> | Time gap (ns, us, ms, s, m) | 10ms | Advances the packet timestamp clock after sending this packet and before the next packet (wait 0ns sends back-to-back). |
| comment "<text>" | Quoted UTF-8 annotation | Omitted | Attaches an Enhanced Packet Block opt_comment annotation when compiling to .pcapng (Wireshark pkt_comment filter). |
| payload "<text>" | hexpayload "<hex>" | Quoted text or hex bytes (choose one) | Omitted | Appends or overrides raw payload bytes ("deadbeef", "de:ad:be:ef", or "\x01\x02") and updates packet lengths and checksums. |
| srcmac <mac> | dstmac <mac> | ethertype <0..65535> | Colon/hyphen/Cisco MAC · EtherType 0..65535 (e.g. 0x0800) | Host MAC / RFC multicast MAC / auto EtherType | Overrides the 14-byte Ethernet II source MAC, destination MAC, or standalone Layer 2 16-bit EtherType. |
| fcs | badfcs | Ethernet CRC-32 trailer flags (choose one) | Omitted | fcs appends a valid IEEE 802.3 4-byte CRC-32 Frame Check Sequence trailer; badfcs XOR-corrupts the CRC-32 for NIC/tap negative tests. |
| vlan <0..4095> [pcp <0..7>] [dei <0|1>] | VLAN ID 0..4095, PCP 0..7, DEI 0..1 | Untagged | Wraps the packet in an IEEE 802.1Q VLAN tag (0x8100) with optional 802.1p QoS priority. |
| qinq <0..4095> [innervlan <0..4095>] | Outer S-VLAN 0..4095, Inner C-VLAN 0..4095 | Untagged (innervlan 1 when qinq is set) | Double-tags the packet with outer IEEE 802.1ad S-Tag (0x88a8) plus inner IEEE 802.1Q C-Tag (0x8100). |
| mpls <0..1048575> [label <0..1048575>] [exp|tc <0..7>] [bos <0|1>] [mplsttl <0..255>] | Repeatable label stack (0..1048575, exp/tc 0..7, bos 0..1, ttl 0..255) | Unlabeled (auto bos=0 on outer labels, bos=1 on bottom) | Prepends one or more 32-bit MPLS label shims (0x8847, e.g. mpls 16000 mpls 24010) ahead of Layer 2 EoMPLS or Layer 3 payloads. |
| ttl <0..255> [dscp <0..63>] [ecn <0..3>] | TTL/Hop Limit 0..255, DSCP 0..63, ECN 0..3 | ttl 64, dscp 0, ecn 0 | Sets IPv4 TTL or IPv6 Hop Limit plus DiffServ (DSCP) and ECN QoS markings. |
| ipid <0..65535> [df] [mf] [fragoffset <0..8191>] [routeralert] [badipchecksum] | IPv4 ID, DF/MF flags, offset 0..8191, Router Alert & checksum fault | ipid 1, flags 0, fragoffset 0, valid RFC 1071 checksum | Sets IPv4 Identification/fragmentation, injects RFC 2113 Router Alert (20 04 00 00), or corrupts the 16-bit IPv4 header checksum (badipchecksum). |
| flowlabel <0..1048575> | 20-bit IPv6 Flow Label (0..1048575) | 0 | Sets the 20-bit IPv6 Flow Label for ECMP routing tests (valid on IPv6 endpoint pairs only). |
| srcport <0..65535> | dstport <0..65535> | Port number 0..65535 | srcport 49152 (remembered), UDP 1234 (or TCP 1234 via transport tcp) | Overrides source or destination port and remembers the port pair automatically on <- replies. |
| transport <tcp|udp|sctp> | tcp, udp, or sctp (dual TCP/UDP + universal L7 SCTP) | transport udp | Switches Layer 4 transport between stateful TCP, connectionless UDP, or Castagnoli CRC-32c SCTP association. |
| badchecksum | nochecksum | L4 checksum fault or UDP zero-checksum flag | Valid RFC checksum / CRC-32c | badchecksum corrupts the L4 checksum for negative firewall/NIC offload tests; nochecksum writes 0x0000 in UDP headers. |
| seq <number> | acknum <number> | win|window <0..65535> | urgent <0..65535> | syn | ack | psh | fin | rst | urg | ece | cwr | TCP sequence/ack numbers, window, flags, SACK, TCP-MD5 & TFO options | psh ack, win 65535, automatic TCP seq/acknum | When using TCP (transport tcp or default TCP): overrides automatic TCP sequence tracking, flags, or mss/wscale/sackperm/sackblock/tsval/tsecr/tcpmd5/tfo. |
Gotchas & Quick Fixes
Swap dst and src BSAP Node IDs on <- RTU Replies
scada -> rtu bsap read dst 50 src 1 seqnum 2 addr 200
scada <- rtu bsap read isresponse dst 1 src 50 seqnum 2 addr 200 value 100Just like DNP3 and ROC Plus, <- swaps Ethernet/IP/UDP addresses automatically, while dst and src explicitly set the application-layer BSAP node fields.
Keep seqnum Within 8-Bit Bounds (0..255)
scada -> rtu bsap poll seqnum 1000scada -> rtu bsap poll seqnum 1BSAP sequence numbers are 1 octet wide (0..=255) and wrap modulo 256.