Industrial ICS/SCADA & IIoT Captures (Modbus, DNP3, S7comm, OPC UA)

Purdue-model OT firewall and passive ICS sensor validation across modbus, dnp3 (reflected 0x3d65 CRC-16), Siemens s7comm, opcua, bacnet, ethernetip CIP, and constrained coap.

Key Takeaways
  • modbus, dnp3, and ethernetip are whitelisted dual-transport protocols supporting both stateful TCP conduits and transport udp I/O polling.
  • dnp3 computes IEEE 1815 reflected 0x3d65 CRC-16s over link headers and 16-byte data chunks automatically (or accepts crc <u16> negative tests).
  • s7comm wraps TPKT + ISO 8073 COTP + Siemens 0x32 PDUs on TCP 102, while opcua frames binary HEL/ACK/OPN/MSG/CLO chunks on TCP 4840.
Companion walkthrough:Poke Firewalls, Suricata & OT
Example 11.016 Ethernet framesFilter: mbtcp || modbus

Modbus TCP Register Poll vs. Modbus-over-UDP Serial Gateway (transport udp)

Tests Purdue Level 2 industrial firewall rules for standard Modbus/TCP polling alongside a serial-to-Ethernet gateway configured for UDP 502.

Wire details: Encodes the 7-byte MBAP header (txid, protoid 0, length, unitid) across both TCP 502 and transport udp.

modbus_tcp_and_udp_conduit.frasm12 lines
Open in Playground
host scada_poller { ip 10.110.10.10 }
host plc_rack_01 { ip 10.110.20.50 }
host rtu_gw_udp { ip 10.110.20.60 }
compile {
scada_poller -> plc_rack_01 tcp syn srcport 50502 dstport 502 win 65535 mss 1460 wait 1ms
scada_poller <- plc_rack_01 tcp syn ack win 65535 mss 1460 wait 1ms
scada_poller -> plc_rack_01 tcp ack wait 1ms
scada_poller -> plc_rack_01 modbus readholdingregisters txid 101 unitid 1 addr 40001 count 4 wait 2ms
scada_poller <- plc_rack_01 modbus readholdingregisters isresponse txid 101 unitid 1 count 4 wait 5ms
scada_poller -> rtu_gw_udp modbus readinputregisters txid 201 unitid 2 addr 30001 count 2 transport udp
}
Terminal Commands (FrameAssembly CLI v3.2.2)
frameassembly modbus_tcp_and_udp_conduit.frasm
Example 11.023 Ethernet framesFilter: dnp3

DNP3 Valid IEEE 1815 CRC-16 vs. Intentional Corrupted CRC Negative Test

Sends a valid UDP 20000 DNP3 Analog Input read (auto CRC-16) followed by an explicit corrupted crc 0xdead packet to verify OT IDS malformed-frame alerts.

Wire details: Omitting crc computes exact reflected 0x3d65 CRC-16s; setting crc 0xdead overrides the link-header checksum intentionally.

dnp3_crc_negative_validation.frasm8 lines
Open in Playground
host sub_master { ip 172.25.0.10 }
host bay_rtu { ip 172.25.0.25 }
compile {
sub_master -> bay_rtu dnp3 read src 1 dst 25 group 30 variation 1 transport udp wait 5ms
sub_master <- bay_rtu dnp3 response src 25 dst 1 group 30 variation 1 transport udp wait 10ms
sub_master -> bay_rtu dnp3 read src 1 dst 25 group 30 variation 1 crc 0xdead transport udp
}
Terminal Commands (FrameAssembly CLI v3.2.2)
frameassembly dnp3_crc_negative_validation.frasm
Protocol references:dnp3(DNP3 (IEEE 1815))
Example 11.035 Ethernet framesFilter: mbtcp || modbus

Minimal Two-Block Modbus TCP (modbus) Quickstart

Smallest zero-boilerplate host + compile capture for Modbus TCP / UDP Industrial Application Protocol (TCP 502 (or UDP 502 via transport udp), Dual-Stack IPv4/IPv6).

Wire details: Defaults to TCP destination port 502 (psh ack), Protocol ID 0, unitid 1, and computes the 16-bit MBAP Length (unitid + PDU bytes) automatically.

modbus_quickstart.frasm10 lines
Open in Playground
host scada_hmi { ip 192.168.100.10 }
host plc_pump1 { ip 192.168.100.50 }
compile {
scada_hmi -> plc_pump1 tcp syn srcport 50502 dstport 502 wait 1ms
scada_hmi <- plc_pump1 tcp syn ack wait 1ms
scada_hmi -> plc_pump1 tcp ack wait 1ms
scada_hmi -> plc_pump1 modbus readholdingregisters txid 1 unitid 1 addr 100 count 2 wait 3ms
scada_hmi <- plc_pump1 modbus readholdingregisters txid 1 unitid 1 count 2 value 1500 isresponse
}
Terminal Commands (FrameAssembly CLI v3.2.2)
frameassembly modbus_quickstart.frasm
Protocol references:modbus(Modbus TCP)
Example 11.045 Ethernet framesFilter: dnp3

Minimal Two-Block DNP3 (IEEE 1815) (dnp3) Quickstart

Smallest zero-boilerplate host + compile capture for Distributed Network Protocol 3 (Electric & Water Utilities) (TCP 20000 (or UDP 20000 via transport udp), Dual-Stack IPv4/IPv6).

Wire details: Defaults to TCP destination port 20000 (transport udp switches to UDP 20000) and builds the 0x0564 Data Link + Transport (FIN|FIR) + Application headers.

dnp3_quickstart.frasm10 lines
Open in Playground
host scada_master { ip 10.100.1.10 }
host sub_rtu_10 { ip 10.100.2.10 }
compile {
scada_master -> sub_rtu_10 tcp syn srcport 52000 dstport 20000 wait 1ms
scada_master <- sub_rtu_10 tcp syn ack wait 1ms
scada_master -> sub_rtu_10 tcp ack wait 1ms
scada_master -> sub_rtu_10 dnp3 read src 1 dst 10 group 30 variation 1 wait 3ms
scada_master <- sub_rtu_10 dnp3 response src 10 dst 1 group 30 variation 1
}
Terminal Commands (FrameAssembly CLI v3.2.2)
frameassembly dnp3_quickstart.frasm
Protocol references:dnp3(DNP3 (IEEE 1815))
Example 11.056 Ethernet framesFilter: s7comm

Minimal Two-Block Siemens S7comm (s7comm) Quickstart

Smallest zero-boilerplate host + compile capture for Siemens S7 Communication Protocol over ISO-on-TCP (TCP 102 (ISO-on-TCP), Dual-Stack IPv4/IPv6).

Wire details: Defaults to TCP destination port 102 (psh ack) and computes the outer 4-byte TPKT (0x03 0x00 <len>) + 3-byte COTP DT (0x02 0xf0 0x80) framing automatically.

s7comm_quickstart.frasm11 lines
Open in Playground
host wincc_hmi { ip 192.168.10.20 }
host s7_plc { ip 192.168.10.100 }
compile {
wincc_hmi -> s7_plc tcp syn srcport 50102 dstport 102 wait 1ms
wincc_hmi <- s7_plc tcp syn ack wait 1ms
wincc_hmi -> s7_plc tcp ack wait 1ms
wincc_hmi -> s7_plc s7comm rosctr "job" setupcomm pduref 1 wait 2ms
wincc_hmi <- s7_plc s7comm rosctr "ackdata" setupcomm pduref 1 wait 2ms
wincc_hmi -> s7_plc s7comm rosctr "job" readvar pduref 2 area 0x84 dbnum 1 offset 0 count 4
}
Terminal Commands (FrameAssembly CLI v3.2.2)
frameassembly s7comm_quickstart.frasm
Protocol references:s7comm(Siemens S7comm)
Example 11.065 Ethernet framesFilter: opcua

Minimal Two-Block OPC UA (opcua) Quickstart

Smallest zero-boilerplate host + compile capture for OPC Unified Architecture Binary TCP Protocol (TCP 4840, Dual-Stack IPv4/IPv6).

Wire details: Defaults to TCP destination port 4840 (psh ack), msgtype "HEL", chunktype "F", and calculates the 4-byte little-endian MessageSize across the entire OPC UA frame.

opcua_quickstart.frasm10 lines
Open in Playground
host historian { ip 10.130.35.10 }
host ua_server { ip 10.130.20.48 }
compile {
historian -> ua_server tcp syn srcport 54840 dstport 4840 wait 1ms
historian <- ua_server tcp syn ack wait 1ms
historian -> ua_server tcp ack wait 1ms
historian -> ua_server opcua msgtype "HEL" chunktype "F" endpointurl "opc.tcp://10.130.20.48:4840" wait 2ms
historian <- ua_server opcua msgtype "ACK" chunktype "F"
}
Terminal Commands (FrameAssembly CLI v3.2.2)
frameassembly opcua_quickstart.frasm
Protocol references:opcua(OPC UA)
Example 11.072 Ethernet framesFilter: coap

Minimal Two-Block CoAP (IoT) (coap) Quickstart

Smallest zero-boilerplate host + compile capture for Constrained Application Protocol (UDP 5683, Dual-Stack IPv4/IPv6).

Wire details: Defaults to UDP destination port 5683 and packs CoAP Version 1, 2-bit Type, Token Length (TKL), 1-byte c.dd Code ((class << 5) | detail), and 16-bit msgid.

coap_quickstart.frasm7 lines
Open in Playground
host sensor_01 { ip 10.70.1.50 }
host iot_gw { ip 10.70.1.1 }
compile {
sensor_01 -> iot_gw coap con post msgid 101 token 0x4a1b uripath "telemetry/humidity" contentformat 50 payload "{\"rh\":48.2}" wait 3ms
sensor_01 <- iot_gw coap ack changed msgid 101 token 0x4a1b
}
Terminal Commands (FrameAssembly CLI v3.2.2)
frameassembly coap_quickstart.frasm
Protocol references:coap(CoAP (IoT))
Example 11.088 Ethernet framesFilter: mbtcp || modbus

Modbus TCP (modbus): Normal Historian Read Polling (FC 3) + Unauthorized Coil/Register Write (FC 5 / FC 6)

Models an HMI polling Holding Registers on Unit 1 (FC 3 request + isresponse reply), followed by a writesinglecoil (FC 5) and writesingleregister (FC 6) command to test OT write-detection alarms.

Wire details: Defaults to TCP destination port 502 (psh ack), Protocol ID 0, unitid 1, and computes the 16-bit MBAP Length (unitid + PDU bytes) automatically. Formats client Request PDUs (addr + count / value) by default, and switches to PLC Response PDUs (byte_count + register/coil values) when isresponse is set.

modbus_ot_conduit_test.frasm15 lines
Open in Playground
host hmi_01 { ip 10.100.10.15 }
host vfd_plc { ip 10.100.20.50 }
compile {
hmi_01 -> vfd_plc tcp syn srcport 51502 dstport 502 win 65535 mss 1460 wait 1ms
hmi_01 <- vfd_plc tcp syn ack win 65535 mss 1460 wait 1ms
hmi_01 -> vfd_plc tcp ack wait 1ms
// 1. Authorized Read Holding Registers (FC 3) + PLC Response (isresponse)
hmi_01 -> vfd_plc modbus readholdingregisters txid 101 unitid 1 addr 0 count 4 wait 2ms
hmi_01 <- vfd_plc modbus readholdingregisters txid 101 unitid 1 count 4 value 3600 isresponse wait 5ms
// 2. Write Single Coil (FC 5) & Write Single Register (FC 6) -> triggers OT IDS write alert!
hmi_01 -> vfd_plc modbus writesinglecoil txid 102 unitid 1 addr 10 value 1 wait 2ms
hmi_01 <- vfd_plc modbus writesinglecoil txid 102 unitid 1 addr 10 value 1 isresponse wait 3ms
hmi_01 -> vfd_plc modbus writesingleregister txid 103 unitid 1 addr 200 value 1800
}
Terminal Commands (FrameAssembly CLI v3.2.2)
frameassembly show modbus_ot_conduit_test.frasm
Example 11.094 Ethernet framesFilter: bacnet || bvlc || bacapp

BACnet/IP (bacnet): Data-Center CRAC Discovery (Who-Is/I-Am), Temperature Read & Setpoint Write

Discovers CRAC device instance 2001, reads Analog-Input 1 Present-Value (propertyid 85), and tests an unauthorized writeproperty setpoint change.

Wire details: Defaults to UDP source and destination port 47808 (0xbac0) and sets BVLC Function to 0x0b (Original-Broadcast-NPDU) on whois/iam or 0x0a (Original-Unicast-NPDU) on readproperty/writeproperty. Bit-packs the 10-bit objecttype and 22-bit objectinstance into the 32-bit ASHRAE 135 BACnetObjectIdentifier tag.

bacnet_dc_cooling_audit.frasm12 lines
Open in Playground
host bms_workstation { ip 192.168.90.10 }
host crac_unit_04 { ip 192.168.90.40 }
compile {
// 1. Device discovery: Who-Is -> I-Am (Object Type 8 = Device, Instance 2001)
bms_workstation -> crac_unit_04 bacnet whois wait 2ms
bms_workstation <- crac_unit_04 bacnet iam objecttype 8 objectinstance 2001 wait 5ms
// 2. Read return-air temperature (Object Type 0 = Analog-Input, Property 85 = Present-Value)
bms_workstation -> crac_unit_04 bacnet readproperty invokeid 10 objecttype 0 objectinstance 1 propertyid 85 wait 4ms
// 3. Write chiller setpoint (Object Type 2 = Analog-Value, Property 85 = Present-Value)
bms_workstation -> crac_unit_04 bacnet writeproperty invokeid 11 objecttype 2 objectinstance 1 propertyid 85 value 24
}
Terminal Commands (FrameAssembly CLI v3.2.2)
frameassembly show bacnet_dc_cooling_audit.frasm
Protocol references:bacnet(BACnet/IP)
Example 11.1010 Ethernet framesFilter: dnp3

DNP3 (IEEE 1815) (dnp3): Substation Analog Input Poll (Group 30) + Select-Before-Operate (Group 12 CROB)

Polls Analog Inputs (group 30 variation 1), receives an RTU unsolicitedresponse event (group 2 Binary Input Change), and executes a two-step select -> operate breaker sequence.

Wire details: Defaults to TCP destination port 20000 (transport udp switches to UDP 20000) and builds the 0x0564 Data Link + Transport (FIN|FIR) + Application headers. Computes the reflected IEEE 1815 0x3d65 CRC-16 across the 8-byte Data Link header and every 16-byte user-data chunk automatically.

dnp3_substation_sbo.frasm18 lines
Open in Playground
host ems_master { ip 172.25.1.5 }
host feeder_rtu { ip 172.25.10.20 }
compile {
ems_master -> feeder_rtu tcp syn srcport 53000 dstport 20000 win 65535 mss 1460 wait 1ms
ems_master <- feeder_rtu tcp syn ack win 65535 mss 1460 wait 1ms
ems_master -> feeder_rtu tcp ack wait 1ms
// 1. Class/Group 30 Analog Input Read + RTU Response
ems_master -> feeder_rtu dnp3 read src 1 dst 20 group 30 variation 1 wait 3ms
ems_master <- feeder_rtu dnp3 response src 20 dst 1 group 30 variation 1 wait 10ms
// 2. RTU Unsolicited Event (Group 2 Binary Input Event) + Master Confirm
ems_master <- feeder_rtu dnp3 unsolicitedresponse src 20 dst 1 group 2 variation 2 wait 2ms
ems_master -> feeder_rtu dnp3 confirm src 1 dst 20 wait 5ms
// 3. Select-Before-Operate (Group 12 Variation 1 CROB) -> triggers high-priority OT alert
ems_master -> feeder_rtu dnp3 select src 1 dst 20 group 12 variation 1 wait 2ms
ems_master <- feeder_rtu dnp3 response src 20 dst 1 group 12 variation 1 wait 2ms
ems_master -> feeder_rtu dnp3 operate src 1 dst 20 group 12 variation 1
}
Terminal Commands (FrameAssembly CLI v3.2.2)
frameassembly show dnp3_substation_sbo.frasm
Example 11.1110 Ethernet framesFilter: s7comm

Siemens S7comm (s7comm): S7 Communication Setup, DB1 Read Poll, DB1 Write & PLC CPU Control Alert

Negotiates S7 PDU parameters (setupcomm), polls 4 bytes from DB1.DBB0 (area 0x84 dbnum 1), writes to DB1, and emits a plccontrol Job to test critical OT security alerts.

Wire details: Defaults to TCP destination port 102 (psh ack) and computes the outer 4-byte TPKT (0x03 0x00 <len>) + 3-byte COTP DT (0x02 0xf0 0x80) framing automatically. Writes the 0x32 S7 Protocol ID, ROSCTR (0x01 Job, 0x02 Ack, 0x03 Ack_Data, 0x07 Userdata), 2-byte error class/code on ackdata, and exact Parameter/Data lengths.

s7comm_plc_security_lab.frasm18 lines
Open in Playground
host tia_ws { ip 10.110.1.15 }
host plc_315 { ip 10.110.2.102 }
compile {
tia_ws -> plc_315 tcp syn srcport 51102 dstport 102 win 65535 mss 1460 wait 1ms
tia_ws <- plc_315 tcp syn ack win 65535 mss 1460 wait 1ms
tia_ws -> plc_315 tcp ack wait 1ms
// 1. S7 Setup Communication (Func 0xf0)
tia_ws -> plc_315 s7comm rosctr "job" setupcomm pduref 100 wait 2ms
tia_ws <- plc_315 s7comm rosctr "ackdata" setupcomm pduref 100 wait 2ms
// 2. Read 4 bytes from Data Block 1 (area 0x84 = DB, dbnum 1, offset 0)
tia_ws -> plc_315 s7comm rosctr "job" readvar pduref 101 area 0x84 dbnum 1 offset 0 count 4 wait 2ms
tia_ws <- plc_315 s7comm rosctr "ackdata" readvar pduref 101 count 4 wait 5ms
// 3. WriteVar (0x05) + PLCControl (0x28) -> critical OT IDS signatures
tia_ws -> plc_315 s7comm rosctr "job" writevar pduref 102 area 0x84 dbnum 1 offset 0 count 2 wait 3ms
tia_ws <- plc_315 s7comm rosctr "ackdata" writevar pduref 102 wait 3ms
tia_ws -> plc_315 s7comm rosctr "job" plccontrol pduref 103
}
Terminal Commands (FrameAssembly CLI v3.2.2)
frameassembly show s7comm_plc_security_lab.frasm
Example 11.129 Ethernet framesFilter: enip || cip

EtherNet/IP (CIP) (ethernetip): PLC Discovery (ListIdentity), Session Registration, CIP Attribute Read & UDP 2222 I/O

Performs a listidentity check, registers session 0x00010042 on TCP 44818, reads Assembly Instance 100 Attribute 3 (Get_Attribute_Single 0x0e), and sends an implicit I/O packet on UDP 2222.

Wire details: Selects TCP port 44818 for explicit encapsulation commands (registersession, listidentity, sendrrdata) and automatically switches to UDP port 2222 on sendunitdata or transport udp. Encodes the 24-byte little-endian EtherNet/IP Encapsulation Header (Command, Length, Session Handle, Status, 8-byte Sender Context, Options).

ethernetip_cip_cell.frasm17 lines
Open in Playground
host studio_ws { ip 10.120.10.15 }
host clx_plc { ip 10.120.10.60 }
compile {
studio_ws -> clx_plc tcp syn srcport 51818 dstport 44818 win 65535 mss 1460 wait 1ms
studio_ws <- clx_plc tcp syn ack win 65535 mss 1460 wait 1ms
studio_ws -> clx_plc tcp ack wait 1ms
// 1. ListIdentity (0x0063) + RegisterSession (0x0065)
studio_ws -> clx_plc ethernetip listidentity wait 2ms
studio_ws -> clx_plc ethernetip registersession context 0x1122334455667788 wait 2ms
studio_ws <- clx_plc ethernetip registersession sessionhandle 0x00010042 context 0x1122334455667788 status 0 wait 3ms
// 2. SendRRData (0x006f): CIP Get_Attribute_Single (0x0e) on Assembly Object (0x04), Instance 100, Attr 3
studio_ws -> clx_plc ethernetip sendrrdata sessionhandle 0x00010042 cipservice 0x0e cipclass 0x04 cipinstance 100 cipattr 3 wait 4ms
// 3. Implicit CIP I/O over UDP 2222 + UnRegisterSession
studio_ws -> clx_plc ethernetip sendunitdata sessionhandle 0x00010042 cipservice 0x0e cipclass 0x04 cipinstance 150 cipattr 3 transport udp wait 3ms
studio_ws -> clx_plc ethernetip unregistersession sessionhandle 0x00010042
}
Terminal Commands (FrameAssembly CLI v3.2.2)
frameassembly show ethernetip_cip_cell.frasm
Example 11.139 Ethernet framesFilter: opcua

OPC UA (opcua): Complete OPC UA Connection (HEL/ACK), OpenSecureChannel, NodeId Read & CLO

Establishes an OPC UA Binary TCP 4840 session across an Industrial DMZ, opens Secure Channel 1, reads "ns=2;s=Turbine1.RPM" via "MSG", and closes cleanly with "CLO".

Wire details: Defaults to TCP destination port 4840 (psh ack), msgtype "HEL", chunktype "F", and calculates the 4-byte little-endian MessageSize across the entire OPC UA frame. Encodes IEC 62541-6 receive/send buffer sizes (65535) + length-prefixed UTF-8 endpointurl inside "HEL" and "ACK" frames.

opcua_idmz_historian.frasm17 lines
Open in Playground
host idmz_hist { ip 172.18.35.20 }
host plant_ua { ip 192.168.48.10 }
compile {
idmz_hist -> plant_ua tcp syn srcport 51840 dstport 4840 win 65535 mss 1460 wait 1ms
idmz_hist <- plant_ua tcp syn ack win 65535 mss 1460 wait 1ms
idmz_hist -> plant_ua tcp ack wait 1ms
// 1. Transport Hello / Acknowledge
idmz_hist -> plant_ua opcua msgtype "HEL" chunktype "F" endpointurl "opc.tcp://192.168.48.10:4840/UA/PlantServer" wait 2ms
idmz_hist <- plant_ua opcua msgtype "ACK" chunktype "F" wait 2ms
// 2. OpenSecureChannel (OPN)
idmz_hist -> plant_ua opcua msgtype "OPN" chunktype "F" securechannelid 0 seqnum 1 reqid 1 wait 2ms
idmz_hist <- plant_ua opcua msgtype "OPN" chunktype "F" securechannelid 1 tokenid 1 seqnum 1 reqid 1 wait 3ms
// 3. Service Read Request (MSG) for NodeId + CloseSecureChannel (CLO)
idmz_hist -> plant_ua opcua msgtype "MSG" chunktype "F" securechannelid 1 tokenid 1 seqnum 2 reqid 2 nodeid "ns=2;s=Turbine1.RPM" wait 4ms
idmz_hist -> plant_ua opcua msgtype "CLO" chunktype "F" securechannelid 1 tokenid 1 seqnum 3 reqid 3
}
Terminal Commands (FrameAssembly CLI v3.2.2)
frameassembly show opcua_idmz_historian.frasm
Protocol references:opcua(OPC UA)tcp(TCP & RFC 7323)
Example 11.144 Ethernet framesFilter: coap

CoAP (IoT) (coap): Confirmable CoAP Sensor GET (2.05 Content) & Missing Resource (4.04)

Queries /sensors/temp over IPv6 receiving a piggybacked ack with code "2.05" JSON payload, then queries an unknown path returning notfound (4.04).

Wire details: Defaults to UDP destination port 5683 and packs CoAP Version 1, 2-bit Type, Token Length (TKL), 1-byte c.dd Code ((class << 5) | detail), and 16-bit msgid. Splits slash-separated uripath strings ("telemetry/humidity") into individual delta-encoded Option 11 (Uri-Path) segments automatically.

coap_ipv6_sensors.frasm11 lines
Open in Playground
host collector { ip 2001:db8:70::1 }
host mote_12 { ip 2001:db8:70::12 }
compile {
// 1. Confirmable GET -> Piggybacked ACK 2.05 Content (contentformat 50 = application/json)
collector -> mote_12 coap con get msgid 500 token 0x0102 uripath "sensors/temp" wait 4ms
collector <- mote_12 coap ack code "2.05" msgid 500 token 0x0102 contentformat 50 payload "{\"c\":22.4}" wait 5ms
// 2. Unknown URI -> 4.04 Not Found
collector -> mote_12 coap con get msgid 501 token 0x0103 uripath "sensors/valve9" wait 4ms
collector <- mote_12 coap ack notfound msgid 501 token 0x0103
}
Terminal Commands (FrameAssembly CLI v3.2.2)
frameassembly show coap_ipv6_sensors.frasm
Protocol references:coap(CoAP (IoT))